Procedure
Preparation
-
Notify all affected employees that a lockout/tagout procedure is about to be performed and the reason for it.
-
Review the system's energy sources (electrical, pneumatic, etc.) and understand the hazards.
-
Electrical Sources:
-
480V, 3-phase, 200A service PER RACK
-
24V, 960W isolated AC-DC Isolated Converter in Primary Rack HV cabinet
-
24Vdc -> 120Vac inverter on shelf under robot controller
-
-
24V, 20A UPS (12V, 7.5Ah SLA batteries x2) inside LV control cabinet (enclosure with HMI screen)
-
-
Pneumatic Sources: ▪ Air Compressor – on shelf under robot controller
- 1 gal capacity, 110 psi
-
Drain on bottom of tank
-
Supplies regulator at base of robot arm
-
-
Trapped air in control circuit between joint 4 and 6 on robot arm
- ¼” tube
Shutdown
-
Power down the PowerHive system by pressing the E-Stop button near the HMI when the robot is at the “Home” position without a battery on the end of the arm.
-
Ensure the robot and all other automated systems are in a fully stopped state.
Isolation
-
Locate and isolate all energy sources:
-
Electrical Power :
- Switch off the main power supply to all high voltage panels (All Rack HV Enclosures – External Handles w/ LOTO capability) using the main disconnect handle.
-
Pneumatic Power :
-
Shut off the air supply at the base-of-arm regulator and drain any residual pressure from the system.
-
Drain the two (2) end of arm tool circuits by alternately pressing the red circuit override switches repeatedly on the joint 4 pneumatic solenoid. (see picture)
-
-
Lockout/Tagout Application
-
Apply lockout devices to each energy isolating device. Ensure that each lock has a unique key.
-
Attach a tag to each lock indicating the following:
-
The name of the person who applied the lock
-
The date and time of application
-
The reason for the lockout
-
-
Verify that the locks and tags are securely attached and clearly visible.
Release Stored Energy
-
Discharge any stored energy by grounding and/or blocking any residual energy sources.
- UPS Battery (Fuse) in LV Box (see picture)
-
Verify that the system is de-energized using a multi-meter or appropriate testing device.
- Grace Technologies Voltage Indicator (R-3W-KB) on each HV enclosure
Verification of Isolation
-
Attempt to start the system using the HMI to ensure that all energy sources are isolated, and the system cannot be powered on.
-
Verify zero energy state by checking for the absence of voltage and air pressure.
Perform Maintenance or Service
-
Conduct the necessary maintenance or service activities on the PowerHive system.
-
Ensure continuous monitoring for any changes in the energy state.
Re-energization
-
After maintenance or service is complete, ensure all tools and personnel are clear of the work area.
-
Notify all affected employees that the system is about to be re-energized.
-
Remove lockout devices and tags. Each lock and tag must be removed by the person who applied it.
-
Reconnect the energy sources:
-
Electrical Power : Reconnect the main power supply at the high voltage panel.
-
oPneumatic Power :-
Open the air supply at the base-of-arm regulator.
-
Close the air/water drain on the air compressor tank.
-
Turn on the air compressor.
-
-
-
Verify the system's functionality by performing a controlled startup using the HMI, then a battery swap or some robot movement after startup.